To ensure internal insulation of electrical equipment from moisture, maintenance personnel will not suffocate from lack of oxygen in the inner working of the device. Adopts low pressure, condensation technique, with the merits of small dimension, light we


  • Product No.: DAG-100(100M3/h)

Details

Application:DAG Transformer dry air generator is widely used in when the transformer and reactor etc large power equipment are been installed and recondition to produce the dry air. To ensure internal insulation of electrical equipment from moisture, maintenance personnel will not suffocate from lack of oxygen in the inner working of the device. It is more secure, more reliable, better economical and more convenient than bottled gas. When the oil filter works in the rainy days and humid environment, equipment box and oil will do the air drying to ensure improve the insulation of oil and reduce the moisture.

Features:1.Adopts low pressure, condensation technique, with the merits of small dimension, light weight, easy operation, energy saving and reliability.
2.With double screw air compressor, low temperature condensed to water technology, etc.
3.Comprehensive utilization of dryer, blot machine, ultra precision filter merits such as scientific combination, produce high quality low dew point of the dry air.
4.The native integration design, compact structure and reasonable, good drying effect, low gas consumption, long working life, composite desiccant use effect is good, service life than ordinary adsorbent extend more than three times.
5.Regenerative adsorption dehydration technology, the high accuracy coalescence dehydration, 0.01μm precision filters to ensure cleanliness.

Functions:DAG series equipment can:
1.Remove moisture from the air. The dew point limit of the treated air can be below -80 °C.
2.Remove particulate matter from the air.
3.The transformer is replaced by nitrogen-filled or hot oil circulating dry overnight.
4.Dry air is supplied during transformer installation and maintenance to ensure dryness inside the transformer.
5.The cylinder is filled with dry air.

Specifications: Model: DAG-100Air supply capacity: 100M3 / Hour
Working pressure: 0.6 ~ 0.8Mpa
Air supply pressure: 0 ~ 0.3Mpa
Air supply dew point temperature: -70Centigrade
Filtration accuracy: 0.01micron
Duty cycle: 5-30Min adjustable
Adsorption material: strong composite molecular adsorbent
Regeneration method: automatically without heating (no heating required)
Running noise: ≤75dB (A)
Working power: 380V, Three-phase three-wire,50Hz (Or As Required)
Total power: 16.5KW
Dimensions: 2150 × 1850 × 2450mm
Equipment weight:1460Kgs
Continuous working time: ≥200 hours

 